Air Conditioning
|
|
Type
|
Central plant, variable air volume
system
|
Central plant, variable air volume
system
|
Central plant, variable air volume
system
|
|
Internal Conditions
|
|
Summer
|
|
Dry Bulb Temperature (°C)
|
22.5°C
|
22.5°C
|
23 +/- 1°C
|
|
Relative Humidity (%)
|
40 60
No humidifiers provided
|
40 60
No humidifiers provided
|
40 60
No humidifiers provided
|
|
Winter
|
|
Dry Bulb Temperature (°C)
|
21.0 °C
|
21.0 °C
|
21.0 +/- 1°C
|
|
Relative Humidity (%)
|
40 60
No humidifiers provided
|
40 60
No humidifiers provided
|
40 60
No humidifiers provided
|
|
|
|
External Design Conditions
|
|
Summer
|
|
Dry Bulb Temperature (°C)
|
32
|
32
|
32
|
|
Wet Bulb Temperature (°C)
|
23
|
23
|
23
|
|
Cooling Towers Capacity (°CWB)
|
24
|
24
|
24
|
|
Winter
|
|
Dry Bulb Temperature (°C)
|
7
|
7
|
7
|
|
|
|
Internal Loads
|
|
Population Density (NLA) Office
|
1 person / 10m2
|
1 person / 10m2
|
1 person / 10m2
|
|
|
|
Lighting (W/m2)
|
15
|
12
|
12
|
|
Equipment Allowance (Central Plant
Sizing) (W/m2)
|
45
|
45
|
25
|
|
Outside Air
|
7.4
|
10
|
|
|
Minimum (L/s/person)
|
7.5
|
7.5
|
7.5
|
|
Condenser Water System Capacity
|
|
|
|
|
Average (NLA) (W/m2)
|
30 (THR)
|
35 (THR)
|
35 (THR)
|
|
Maximum for One Floor (W/m2)
|
80 (THR)
|
80 (THR)
|
80 (THR)
|
|
Water Temperature
|
31C in / 36.5C out
|
31C in / 36.5C out
|
32C in / 38C out
|
|
Filtration
|
|
Average over the life of the media
|
|
Dust No: 1 (%)
|
40
|
40
|
40
|
|
Dust No: 2 (%)
|
98
|
|
98
|
|
Dust No: 3 (%)
|
90
|
|
90
|
|
Dust No: 4 (%)
|
80
|
85
|
80
|
|
Maximum Noise Levels
|
|
Office areas (NR)
|
42
|
43
|
35
|
|
Normal Hours Of Operation of Air Conditioning
Plant
|
|
|
|
|
Comfort Conditions
|
8:00am
6:00pm Week Days
|
7:00am
6:00pm Week Days
|
8:00am
6:00pm Week Days
|
|
After Hours Air Conditioning
|
|
Review.
|
Yes
|
Yes
|
Yes
|
|
Cost (subject to annual
review and adjustment)
|
|
|
|
|
Whole Floor ($/hour)
|
Price on Application
|
Price on Application
|
Price on Application
|
|
Third of Floor ($/hour)
|
N/A
|
N/A
|
N/A
|
|
|
|
Zones per Floor
|
|
Perimeter
|
1 CV unit / elevation
|
1 CV unit / main elevation and
corner
|
12 VAVs/floor
|
|
Internal
|
Approximately 21 VAVs/floor
|
Approximately 21 VAVs/floor
|
Approximately 10 VAVs/floor
|
|
General Exhaust Riser
|
|
Capacity
|
|
Average per Floor (L/s)
|
150
|
250
|
(L/s/mē NLA) 0.2
|
|
Maximum for One Floor (L/s)
|
300
|
500
|
(L/s/mē NLA) 0.5
|
|
Toilet Exhaust Spare Capacity
(L/s per floor)
|
-
|
100
|
-
|
|
Supplementary Fresh Air Riser
|
|
Capacity
|
|
Average per Floor (L/s)
|
100
|
200
|
200
|
|
Maximum for One Floor
|
500
|
500
|
500
|
|
Return Air Through Ceiling Space
|
|
Through ceiling space to west end of core to
RA riser
|
Yes
|
Yes
|
Yes
|
|
|
|
Smoke Spill System to Office Floors
|
|
Smoke extraction
|
AS1668-1 (1991)
|
E2.2BCA AS 1668.1 (1991)
|
AS1668-1 (1991)
|
|
|
|
Building Monitoring and Control System
|
|
Type
|
Satchwell BAS2800+
|
Honeywell
|
Honeywell
|
|
Availability for Tenancy Monitoring (subject
to approval)
|
Yes
|
Yes
|
Yes
|
|
|
|
Building Envelope
|
|
Glazing
|
|
SC Maximum
|
0.26
|
0.26
|
0.29ASHRAE
|
|
U Maximum (w/m2K)
|
15.9
|
15.9
|
1.8
|
|
|
|
Provision for Internal Blinds
|
Yes
|
Yes
|
Yes
|